Optical Transmission
Optical Multiplexer

VCL Products > Optical Transmission > Optical Multiplexer

VCL-9025, 4 Channel / 8 Channel Optical Multiplexer

Get Data Sheet

The Valiant VCL-9025, Optical Multiplexer using WDM (Wave Division Multiplexing) technology is designed to serve Utility and SCADA applications and address the security issues pertaining to critical infrastructure assets. It can be used for the implementation of IT and OT networks over a single fiber pair which include 10G, SDH / SONET as well as Teleprotection (Distance Protection and Line Differential Protection) applications, while preserving the security and reliability of IEC 60834 requirements.


Each of the 4 / 8 optical channels are physically multiplexed into a single FIBER on the transmit side. Similarly, each of the 4 / 8 receive channels are multiplexed into a single FIBER on the receive side. 4 / 8 distinctly separate optical channels are transmitted / received on a single optical fiber pair. It is equivalent to using 4 / 8 separate optical fiber pairs instead of a single optical fiber pair to transmit / receive the 4 / 8 x optical channels. This is made possible by using WDM technology that use specific wavelengths in the WDM band to physically transmit and receive 4 / 8 channels on a single fiber pair instead of using white lasers that would only have the capability to transmit one single optical channel of each fiber.

The VCL-9025 optical multiplexer ensures complete security and reliability through physical separation, because each of the 4 / 8 optical channels are transmitted completely independently of each other – even though they are being transmitted on a single optical fiber pair.

VCL-9025 Optical Multiplexer using WDM technology in optical fiber communication systems significantly increases the capacity of the network. This helps in increased bandwidth capacity of the fiber, allowing for the transmission of more data and supporting higher data rates.

Features

  • Low Insertion Loss
  • Wide Passband
  • Very High Channel Isolation. Suitable for multiplexing IT and OT transmission links over a single optical fiber pair without compromising cyber-security.
  • High stability and reliability over an extended temperature range.
  • Compact size

Application Scenarios:

Multiplexing up to 4 / 8, 10G Ethernet, 1G Ethernet, STM-1, STM-4, STM-16, IEEE C37.94 Differential Protection Channels, in any combination, over a single optical fiber pair.

Application Diagram:


VCL-2145-LC Application

Technical Specifications

Parameter Unit Values
Channels CH 4 / 8
Centre Wavelength nm 1471, 1491, 1511, 1531, 1551, 1571, 1591, 1611
Passband Channels min. nm ± 6.5
Isolation Mux Adjacent Channel Min. dB 30
Non-adjacent Channel Min. 45
Demux Adjacent Channel Min. 30
Non-adjacent Channel Min. 45
Insertion Loss Max. dB 1.8
Ripple in Passband Max. dB 0.5
Directivity Min. dB 55
Polarization Dependent Loss Max. dB 0.2
Polarization Mode Dispersion Max. ps 0.10 (GD)
Return Loss Min. dB 50
Power Handling Max. mW 500
Fiber Type 1510n, Single Mode, Corning SMF-28 or Equivalent
Connector Type LC


Valiant Communications is an ISO 9001:2015, ISO 10001:2018, ISO 14001:2015, ISO 27001:2013 and ISO 45001:2018 certified equipment manufacturer.